PALJET
| Type | 374ML | 374M | 374P | 374Q |
|---|---|---|---|---|
| Input control singnal | 1.Analog signal: DC 4-20mA (input impedance 250Ω, rising characteristic), other types can be optionally configured (such as DC 1-5V, etc.).2.Switching signal: Passive dry contact, DC 24V or AC 220V.3.Fieldbus signal: Supports Modbus-RTU, Profibus-DP V0/V1, HART, FF, etc. (This perfectly corresponds to the "adaptable bus interface" promoted in the previous picture, and the onfiguration is very rich). | |||
| Output control singal | 1.Analog signal (feedback): DC 4-20mA, load resistance ≤750Ω, temperature effect ≤0.1%/10k, rising characteristic.2. Digital signal (relay output): Up to 9 groups of isolated relay outputs, contact capacity is 3A 250VAC or 3A 30VDC. (Can meet complex interlocking control requirements) | |||
| (Max. output | 100000N | 10000Nm | 250000Nm | 1800Nm |
| Power source | 1.Three-phase three-wire AC380V±10% 50Hz, ±1%, harmonic content <5%. (Suitable for high-power industrial sites)2.Optional power supply: DC24V, 48V, 84V.3.Other AC power supplies: AC110V, 220V, 380-660V, 50Hz/60Hz (if these non-standard power supplies are required, please specify when ordering) | |||
| Deadband | Adjustable from 0.5% to 5.0% | |||
| Ambient Temperatur | Standard: -25℃ ~ +60℃ .Optional: -40℃ ~ +70℃ (Adaptable to extreme cold or high-temperature environments). | |||
| Explosionproof grade | Protection rating: IP67, IP68 (2 meters underwater for 2 hours). (Top-tier protection capability, can be submerged in water for a short period).Explosion-proof rating: Ex db IIC T4 Gb. (Updated compared to the ExdIIBT4/ExdIICT4 standard in the previous table, belongs to the highest level of IIC flameproof protection, suitable for environments containing the most dangerous gases such as hydrogen and acetylene). | |||
Note: The above information is released by KOSO and reviewed by Engineer Huang Zhi from Paljet.
Next product: 3730 Series Electronic‑Hydraulic Actuators